Overview
Energy savings due to increased system efficiency with Q-Limit function (flow limitation)
Optimised display for improved readability and control
Installation in small spaces thanks to compact design and position-independent LCD display
Modular concept for connection to all common bus systems (e.g. Modbus, BACnet, CAN, LON, PLR)
Corrosion-resistant pump housing made of bronze for applications with possible oxygen intrusion
Proven quality and reliability
Typesetting program
After 19 years of success, the Wilo-Stratos high-performance pump will be completely removed from the product range and replaced by the new Wilo-Stratos MAXO smart pump by the end of March 2020. The new Wilo-Stratos MAXO pump technology will continue the success of the Stratos series.
Type
Glandless circulation pump with threaded connection or flange connection, EC motor and automatic speed control.
Application
All types of drinking water circulators, all hydronic heating systems, air-conditioning systems and closed cooling circuits, industrial circulation systems
Equipment/function
Modes of operation
- Manual operation (n = constant)
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- Δp-T for differential pressure dependent on temperature control (programmable via IR-Stick, IR-Monitor, Modbus, BACnet, LON or CAN)
- Q-Limit to limit max. flow (can only be set on the IR-Stick)
Manual control
- Setting of operating modes
- Setting the flow rate value
- Setting for automatic speed reduction mode
- Pump ON/OFF setting
- Speed setting (manual switch-over)
Automatic control
- Infinitely variable speed control according to mode of operation
- Automatic downmilling operation
- Lockout function
- Soft start
- Full motor protection with integrated electronic shutdown
External control
- Priority off control input (possible with Stratos IF-modules)
- Minimum power priority input (available with Stratos IF-modules)
- Control input "Analog In 0 - 10V" (remote speed switching), possible with Stratos IF-modules
- Control input "Analog In 0 - 10 V" (remote setpoint adjustment), possible with Stratos IF-modules
Alarms and display
- Generalized fault indication (potential free NO contact)
- Separate fault indication (potential free normally open contact), possible with Stratos IF-Modules
- Lighted fault indicator
- LCD display for the indication of pump parameters and error codes
Data exchange
- Infra-red interface for wireless data exchange with IR-Stick/IR monitor
- Modbus RTU serial digital interface for connection to a building automation system via RS485 bus system (possible with Stratos IF-modules)
- BACnet MS/TP Slave serial digital interface for connection to a building automation system via RS485 bus system (possible with Stratos IF-modules).
- CAN serial digital interface for connection to a building automation system via CAN bus system (possible with Stratos IF-modules)
- LON serial digital interface to connect to a LONWorks network (available with Stratos IF-modules)
- PLR serial digital interface for connection to a building automation system via a Wilo interface converter or special communication modules (available with Stratos IF-Modules)
Twin pump control (twin pump or two single pumps)
- Main/standby operation (automatic switchover in the event of malfunction/pump timer operation): various combinations with Stratos IF-Modules (accessories) possible
- Dual pump operation (switch-on of second pump during peak demand with efficiency optimisation): various combinations with Stratos IF-Modules (accessories) possible
Accessories
- Keyed casting on pump casing (for pumps with threaded pipe connection P2 ≤ 100 W)
- For pumps with flange connection: flange design
- Standard version for pumps DN 40 to DN 65: Combination flange PN 6/10 (flange PN 16 as per EN 1092-2) for counter flanges PN 6 and PN 16
- Special version for pumps DN 40 to DN 65: Flange PN 16 (acc. EN 1092-2) for counter flange PN 16,
- Socket for the optional addition of Wilo IF-Modules
- Thermal insulation as standard