Designed for measuring and metering active or reactive electrical energy in single or multi-tariff mode.
The meter can be used autonomously or as part of automated control and metering systems for electricity (ASKUE).
Calibration interval - 16 years;
Average service life - 32 years;
Mean time between failures - 318 160 hours;
The service life of the meter from one lithium battery is at least 16 years.
Technical data | |
---|---|
Mains frequency | 50±2,5 Gz |
Full and active power consumed by each voltage circuit at rated voltage and rated frequency, VA, not more | 10 (2,0) Вт |
Apparent power consumed by each current circuit at rated voltage and rated frequency, VA, not more | 0,3 Вт |
Specified operating voltage range | (0,9...1,1) Uном, В |
Extended operating voltage range | (0,8...1,15) Uном, В |
Limiting operating voltage range | (0...1,15) Uном, В |
Mains voltage measuring range | 175...310 |
Basic relative error of voltage measurement | 0,5 % |
Basic relative error of current measurement | 0,5% |
Mains frequency measurement range | 45...55 Gz |
Basic relative error of mains frequency measurement | 1% |
The accuracy of the watch under normal conditions | ±0,5 s / day |
Lithium battery life hours | 16 лет |
Protection of information | Seal, tamper switch and warranty sticker |
Initial start-up of the counter | 5 sec. no more |
Indicator type | Liquid crystal |
The number of bits of the reading device | 8 |
Low-order unit. when displaying energy | 0,01 kWh |
Operating temperature range | -40... +60 °С |
Storage temperature range | -40... +70 °С |
Relative humidity,% no more at temp. +25°С | 98 °С |
Atmosphere pressure | 60... 106,7 кPа |
Counter weight | 0,8 kg |
Average service life of the counter | 32 years |
Mean time to failure | 318 160 h |
dimensions | 70 x 150 x 102 мм |
Accuracy class when measuring active energy according to GOST 31819.21 | 1; 0,25 |
Accuracy class for measuring reactive energy according to GOST 31819.23 | 2; 1 |
Current measurement range, A | 0,1Iб…Iмакс |
Basic / maximum current Ib / Imax, A (accuracy class 1/2) | 5/60; 5/100 |
Basic / maximum current Ib / Imax, A (accuracy class 0,25/1) | 5/7,5 |
Starting current when measuring active / reactive energy, mA (accuracy class 1/2) | 20/25 |
Starting current when measuring active / reactive energy, mA (accuracy class 0,25/1) | 5/10 |
Passport - Three-phase electronic meters "PULSAR" 3 / 3T-1 / 2K-10 / 100-1-2 (multi-tariff, LCD, RS485, direct connection, 10 (100) A, automenu) | Download |
Passport - Three-phase electronic electricity meters "PULSAR" 3 / 3T-05 / 1K-5 / 7.5-1-2 (multi-tariff, LCD, RS485, semi-indirect inclusion, 5 (7.5) A, automenu) | Download |