Article: Н00010627
Interface | M-Bus |
Data archive in non-volatile memory | 60 months, 184 days, 1488 hours |
Flowmeter | 1 flow meter |
Du | DN65 |
Rated flow qp | 50 m3/h |
Pipeline | straight |
Number of pulse inputs | 3 pulse inputs |
Max temperature | 150 °C |
Presence of pressure sensors | with pressure sensors |
Minimum flow, qi, m3/h | 0.5 |
Maximum flow rate, qs, m3/h | 100 |
Sensitivity threshold, m3/h | 0.07 |
Number of pressure sensors, pcs | 2 |
Pressure loss at qp, MPa | <0.225 |
Metrological class (EN1434) | 2 |
Dynamic range of flow measurement qi/qp | 1:1000 |
Nominal pressure, MPa | 1.6 |
Temperature difference measurement range, °C | 3—104 |
Temperature difference to start energy counting, °C | 0.25 |
Heat unit | Gcal |
Connecting thread | G2B |
Length, mm | 200 |
Presence of a metal hose | without metal hose |
Household heat meter with radio output "Pulsar IoT" - designed to measure: the amount of heat energy, cooling energy, heat power, volumetric flow (volume), temperature, temperature difference of the coolant (water). To read the data, access to the metering device is not required - the transmission is carried out to the dispatching device via a radio channel. Using a radio channel allows you to transmit information regardless of the presence of a cellular signal. The radio module is a self-contained device - it works from a built-in battery. Structurally, heat meters are a single heat meter and consist of:
The principle of operation of the heat meter consists in the processing by the calculator of the measurement signals coming from the volumetric flow sensor (s), temperature sensors, gauge (sensors) of excess pressure, calculation and display on the indicator device of the calculator of the measurement results.
Features of the | Ду15 | Ду15 | Ду15 | Ду20 | Ду25 | Ду25 | Ду32 | Ду40 | Ду50 | Ду50 | Ду65 | Ду65 | Ду80 | Ду80 | Ду100 | Ду100 | Ду125 | Ду125 | Ду150 | Ду150 | Ду200 |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Minimum volumetric flow, qi, m3 / h | 0,006 | 0,012 | 0,015 | 0,025 | 0,035 | 0,06 | 0,06 | 0,1 | 0,15 | 0,35 | 0,25 | 0,5 | 0,4 | 0,8 | 0,6 | 1,2 | 1 | 2 | 1,5 | 3 | 2 |
Maximum volume flow, qp, m3 / h | 0,6 | 0,6 | 1,5 | 2,5 | 3,5 | 6 | 6 | 10 | 15 | 35 | 25 | 50 | 40 | 80 | 60 | 120 | 100 | 200 | 150 | 300 | 500 |
Limiting volumetric flow, qs, m3 / h | 1,2 | 1,2 | 3,5 | 6 | 7 | 12 | 15 | 20 | 30 | 70 | 50 | 100 | 80 | 160 | 120 | 240 | 200 | 400 | 300 | 600 | 1000 |
Sensitivity threshold, m3 / h | 0,002 | 0,002 | 0,003 | 0,005 | 0,007 | 0,02 | 0,012 | 0,02 | 0,03 | 0,07 | 0,05 | 0,07 | 0,08 | 0,1 | 0,15 | 0,2 | 0,24 | 0,28 | 0,3 | 0,35 | 0,35 |
Connecting thread | G3/4B | G3/4B | G3/4B | G1B | G1 1/4B | G1 1/4B | G1 1/2B | G2B | |||||||||||||
Length, mm | 110 | 110 | 110 | 130 | 160 | 160 | 180 | 200 | 200 | 200 | 200 | 200 | 225 | 225 | 250 | 250 | 250 | 250 | 300 | 300 | 350 |
Универсальное приложение для работ по пусконаладке оборудования «Пульсар». Подходит для настройки приборов учета и счетчиков импульсов-регистраторов.
Version dated 08/05/2021.
Universal application for commissioning Pulsar equipment.
Suitable for setting up metering devices and pulse counters-recorders.
IoT installer. Designed for configuring radio transmitters.
In the case when the current settings of the converter are unknown, you can use the network device search utility.
Software for setting up electricity meters "Pulsar" during commissioning.
When starting the program, select the device in the "Object Tree". The set of tabs depends on the selected object or group of objects.
Types of tabs:
Подходит для автоматизированного учета в отдельных многоквартирных домах и жилищных комплексах:
Suitable for automated accounting in individual apartment buildings and housing complexes:
Для автоматизированного учета управляющих компаний, ТСЖ, ресурсоснабжающих организаций
Программное обеспечение PULSAR SET (совместно с SANKOM): Осуществляет подбор отопительных приборов, диаметров трубопроводов и запорно-регулирующей арматуры Определяет настройки балансировочных клапанов, клапанов терморегуляторов на подводках к отопительным приборам Составляет подробную спецификацию оборудования Позволяет использовать несколько источников тепла (холода) в одном проекте, что применимо при проектировании, например, четырехтрубных систем
— CO 7.2 Basic module (heating and ventilation)
— H2O 7.2 Basic module (water supply and sewerage)
(water supply and sewerage)
Расчёт гидравлических потерь — теплосчетчики «Пульсар»
We will tell you in detail about our services, types of work and typical projects, calculate the cost and prepare an individual offer!